- ONLINE UPS
- True double-conversion
- Microprocessor control optimizes reliability
- Input power factor correction 0.99
- Output power factor 0.8
- Wide input voltage (110 V–300 V)
- Converter mode available
- ECO mode for energy saving
- Generator compatible
Adjustable battery numbers only available for 6K and up models
- Smart SNMP works well with either USB or RS-232 together
Emergency power off function only available for 6K and up models
SKU | ME-3000-WPTU |
---|---|
Weight | 27.6000 |
Physical Dimensions | 421 x 190 x 318 (mm) |
Capacity | 3000 VA / 2400 W |
Voltage Range Low Line Transfer | 160VAC/140VAC/120VAC/110VAC±5% ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) |
Voltage Range Low Line Comeback | 168VAC/148VAC/128VAC/118VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) |
Voltage Range High Line Transfer | 300 VAC ± 5 % |
Voltage Range High Line Comeback | 290 VAC ± 5 % |
Frequency Range | 40Hz ~ 70 Hz |
Phase | Single phase with ground |
Power Factor | ≧ 0.99 @ nominal voltage (input voltage) |
Output Voltage | 200/208/220/230/240VAC |
AC Voltage Regulation (Batt. Mode) | ±1% (Batt. Mode) |
Frequency Range (Synchronized Range) | 47 ~ 53 Hz or 57 ~ 63 Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz |
Overload | Sounding twice every second |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≦ 3 % THD (linear load) ≦ 6 % THD (non-linear load) |
Waveform (Batt. Mode) | Pure Sinewave |
AC to DC | Zero |
Inverter to Bypass | 4 ms (Typical) |
AC Mode | 90% |
Battery Mode | 88% |
Battery Type | 12 V / 9 AH |
Numbers | 6 |
Recharge Time | 4 hours recover to 90% capacity (Typical) |
Charging Current | 1.0 A (max.) |
Charging Voltage | 82.1 VDC ±1% |
Battery Type & Numbers | No |
Charging Current | No |
Charging Voltage | No |
Humidity | 20-90 % RH @ 0- 40°C (non-condensing) |
Noise Level | Less than 50dBA @ 1 Meter |
Optional USB/RS-232 Port | Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC |